Dust and drip proof construction. (designed to IEC 60529 IP54) | |
• | Designed to meet IEC 61010-1 and IEC 61557 safety standard. |
• | 1mA rated test current at the minimum resistance. |
• | 200mA measuring current on continuity testing. |
• | Automatic discharge of circuit capacitance. (Any charge stored in the circuit under test will be automatically discharged after testing.) |
• | Live circuit warning buzzer and neon lamp. |
• | Small and lightweight. Shock resistant new case material. |
• | AC voltmeter with linear, easy-to-read scale. |
• | Operates on AA, R6P×6 dry batteries. |
Insulation Resistance | |
Test Voltage | 250V/500V/1000V |
Measuring Ranges (Mid-scale Value) |
100MΩ/200MΩ/400MΩ (1MΩ) (2MΩ) (4MΩ) |
Output Voltage on open circuit |
Rated test voltage+20%, -0% |
Nominal Current | 1mA DC min. |
Output Short Circuit Current |
1~2mA DC |
Accuracy | 0.1~10MΩ/0.2~20MΩ/0.4~40MΩ (Accuracy Guaranteed Ranges) ±5% of indicated value |
Continuity | |
Measuring Ranges (Mid-scale Value) |
3Ω/500Ω (1.5Ω) / (20Ω) |
Output Voltage on open circuit |
4.1V DC approx. |
Measuring Current | 210mA DC min. |
Accuracy | |±1.5% of scale length |
AC Voltage | |
AC Voltage | 0~600V AC |
Accuracy | |±5% of scale length |
General | |
Safety Standard | IEC 61010-1 CAT.III 600V Pollution Degree 2 IEC 61010-2-031 IEC 61557-1/2/4 |
IP Rating | IEC 60529-IP54 |
EMC Standard | IEC 61326-1 |
Withstand Voltage | 3700V AC for 1 minute |
Power Source | R6P (AA) (1.5V) × 6 |
Dimensions | 106(L) × 160(W) × 72(D)mm |
Weight | 560g approx. |
Accessories | 7122B (Test leads) Pouch for test leads 8923 (F500mA/600V fuse) × 2 R6P (AA) × 6 Shoulder Strap Instruction Manual |